top of page

Electronic Control for Voltage Regulators – CTR-4 

ctr4 - itb.png

Applications:

Single-phase/three-phase control for single-phase voltage regulator banks. (compatible with all brands)

Technical characteristics:

  • Knife switches for short-circuiting the current transformer (CT).

  • Manual switches for starting the motor.

  • Single-phase or three-phase regulation (synchronized with other CTR-4 controls in the same bank via fiber optic communication)

  • Compartment for radio/modem installation.

  • 20x4 digit display with backlight.

  • Tap audit function.

  • Fixed difference function for the master when in three-phase mode.

  • Degrees of freedom function (for free single-phase regulation).

  • Standardized connection interface (standard pinout from 1 to 10).

  • Enclosure with IP54 and IK9 protection rating.

  • Enclosure constructed of carbon steel.

  • Nine power flow treatment modes.

  • DNP3.0 level 2 communication protocol with point remapping capability.

  • Provision for cable routing for automation.

  • Selector for switching the light from neutral to phase or neutral.

  • Motor current sensor.

  • Standby system to preserve display life and reduce power consumption.

  • Freeware software for parameterization and capture of records (mass storage).

  • Bracket for mounting to the tank or on a pole.

  • Numeric keypad for quick adjustment.

  • Power supply from 90 to 145Vac.

  • Three digital inputs and DNP3.0 points are available to send messages to the supervisory system.

  • Three simultaneous communication ports.

  • Three programmable logic outputs.

Optional features:

  • Cables with electrostatic shielding.

  • Cables with lengths as per customer specifications.

  • Communication interface converters.

  • Protocol converters.

  • Alternative finish colors.

  • Frontal in English and Spanish.

  • Internal lighting of the enclosure.

  • Enclosure with IP65 protection rating.

  • Enclosure constructed of stainless steel.

  • Door sensor.

  • Heating system.

  • Uninterruptible power supply (UPS) system.

  • Painting system for harsh environments.

Measurements:

  • Three-phase input counter.

  • Transaction counter.

  • Neutral current.

  • Current on the load side and on the source side.

  • Power factor.

  • Frequency.

  • Total harmonic current and up to 15A.

  • Total harmonic tension and up to the 15th.

  • Apparent, active, and reactive power.

  • Voltage on the load and source sides.

Functions:

  • Overcurrent blocking.

  • Maximum and minimum position locks.

  • Automatic load bonus.

  • Short-circuit current setting.

  • Configuration for remote communication.

  • Control of the tap audit routine.

  • Date & time.

  • Voltage and current phase shift.

  • Fixed difference to master.

  • Degree of freedom.

  • Enables regulator.

  • Current threshold for reverse flow detection.

  • Maximum and minimum voltage limiters.

  • Switch reading method.

  • Mode to trigger regulation.

  • Power flow treatment modes.

  • TP and TC ratio.

  • Selects the master regulator.

  • Password for operation and administration levels.

  • Record acquisition time.

  • Time for neutralization via uninterruptible power supply (UPS).

  • Inverse timing.

  • Switch actuation type.

  • Regulator bank connection type.

  • Regulator type “A” or “B”.

  • A regulation profile for direct flow (+3 dynamic profiles depending on the load current).

E-MAILS

General: itb@itb.ind.br

Commercial: vendas@itb.ind.br

Central: (18)3643-8000

Commercial: (18) 3643-8010

Shopping: (18) 3643-8020

FOLLOW ITB!

  • LinkedIn
  • Facebook
  • Instagram

ADDRESS

PHONES

161 Devanir Terence Street – Raif Mehana Rahal Industrial Park.
Birigui – SP – CEP 16.206-012

bottom of page